Final Drawing Review · Review DR-1042

Lumen Coffee Roasters Suite A-140

In Review·Northgate Town Center·Required review date Aug 11, 2026 (1 days remaining)

Property

Northgate Town Center

Tenant Contact

Kara Bell

Tenant Architect

Owen Pratt, AIA

Assigned Reviewer

Dana Whitfield

Submission Date

Jul 28, 2026

Applicable Criteria

v3.5 manual

Comment Log

Categorized comments issued to the tenant team

  • 01ArchitecturalSheet A-201Open

    Storefront head height does not meet the 10'-0" clear minimum at Zone A frontage.

    Reviewer: Dana Whitfield

  • 02StructuralSheet S-101Tenant Response Received

    Provide landlord structural engineer review for the two new RTU curbs and associated framing.

    Tenant responseStructural calculations from Kessler Engineering will be issued with the permit set.

    Reviewer: Dana Whitfield

  • 03PlumbingSheet P-102Open

    Annotate grease interceptor size and location; coordinate tie-in with landlord sanitary main.

    Reviewer: Jordan Meeks

  • 04AccessibilitySheet A-121Resolved

    Confirm 60" turning radius at the rear restroom; dimension string appears to conflict.

    Tenant responseRestroom enlarged 4" — see revised plan.

    ResolutionVerified on Rev 2 drawings.

    Reviewer: Dana Whitfield

  • 05Landlord CriteriaSheet A-401Open

    Neutral pier finish must match landlord standard; specified finish is not an approved material.

    Reviewer: Dana Whitfield

  • 06Utility CoordinationSheet E-101Not Applicable

    Electrical service size exceeds allocated panel capacity for Suite A-140.

    ResolutionLandlord confirmed spare capacity in panel LP-2.

    Reviewer: Jordan Meeks

Add Comment