Final Drawing Review · Review DR-1042
Lumen Coffee Roasters Suite A-140
Property
Northgate Town Center
Tenant Contact
Kara Bell
Tenant Architect
Owen Pratt, AIA
Assigned Reviewer
Dana Whitfield
Submission Date
Jul 28, 2026
Applicable Criteria
Comment Log
Categorized comments issued to the tenant team
- 01ArchitecturalSheet A-201Open
Storefront head height does not meet the 10'-0" clear minimum at Zone A frontage.
Reviewer: Dana Whitfield
- 02StructuralSheet S-101Tenant Response Received
Provide landlord structural engineer review for the two new RTU curbs and associated framing.
Tenant responseStructural calculations from Kessler Engineering will be issued with the permit set.
Reviewer: Dana Whitfield
- 03PlumbingSheet P-102Open
Annotate grease interceptor size and location; coordinate tie-in with landlord sanitary main.
Reviewer: Jordan Meeks
- 04AccessibilitySheet A-121Resolved
Confirm 60" turning radius at the rear restroom; dimension string appears to conflict.
Tenant responseRestroom enlarged 4" — see revised plan.
ResolutionVerified on Rev 2 drawings.
Reviewer: Dana Whitfield
- 05Landlord CriteriaSheet A-401Open
Neutral pier finish must match landlord standard; specified finish is not an approved material.
Reviewer: Dana Whitfield
- 06Utility CoordinationSheet E-101Not Applicable
Electrical service size exceeds allocated panel capacity for Suite A-140.
ResolutionLandlord confirmed spare capacity in panel LP-2.
Reviewer: Jordan Meeks